EMF behind transient reactance (EBTR) model of a synchronous generator has
widely been used in the studies of power system stability. The damping in t
he quadrature axis of a synchronous machine is normally represented by a si
ngle time constant equivalent circuit. However, the presence of field in ad
dition to the damper circuit in the direct axis of the machine makes modell
ing difficult in the direct axis based on the emf behind transient reactanc
e. As a result approximate representations are normally employed. The model
s based on appropriate representations do not produce accurate results. In
this paper, an accurate comprehensive model for the direct axis is presente
d. The development emerges from the detailed representation of the machine
with fluxes as the state variable. The emfs behind field and d-axis damper
transient reactances are considered in the model. The validity of the model
is tested by comparison with the responses obtained from a detailed model
[1]. (C) 2000 Elsevier Science S.A. All rights reserved.