A comprehensive EMF behind transient reactance (EBTR) model for power system stability study

Citation
Sml. Kabir et al., A comprehensive EMF behind transient reactance (EBTR) model for power system stability study, ELEC POW SY, 53(3), 2000, pp. 217-222
Citations number
9
Categorie Soggetti
Eletrical & Eletronics Engineeing
Journal title
ELECTRIC POWER SYSTEMS RESEARCH
ISSN journal
03787796 → ACNP
Volume
53
Issue
3
Year of publication
2000
Pages
217 - 222
Database
ISI
SICI code
0378-7796(20000301)53:3<217:ACEBTR>2.0.ZU;2-A
Abstract
EMF behind transient reactance (EBTR) model of a synchronous generator has widely been used in the studies of power system stability. The damping in t he quadrature axis of a synchronous machine is normally represented by a si ngle time constant equivalent circuit. However, the presence of field in ad dition to the damper circuit in the direct axis of the machine makes modell ing difficult in the direct axis based on the emf behind transient reactanc e. As a result approximate representations are normally employed. The model s based on appropriate representations do not produce accurate results. In this paper, an accurate comprehensive model for the direct axis is presente d. The development emerges from the detailed representation of the machine with fluxes as the state variable. The emfs behind field and d-axis damper transient reactances are considered in the model. The validity of the model is tested by comparison with the responses obtained from a detailed model [1]. (C) 2000 Elsevier Science S.A. All rights reserved.