VOLTAGE DISTORTION IN DISTRIBUTION FEEDERS WITH NONLINEAR LOADS

Citation
Ae. Emanuel et al., VOLTAGE DISTORTION IN DISTRIBUTION FEEDERS WITH NONLINEAR LOADS, IEEE transactions on power delivery, 9(1), 1994, pp. 79-85
Citations number
3
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
9
Issue
1
Year of publication
1994
Pages
79 - 85
Database
ISI
SICI code
0885-8977(1994)9:1<79:VDIDFW>2.0.ZU;2-D
Abstract
The voltage of three real-life 13.8kV feeders supplying customers with non-linear loads was analyzed by means of computer simulations. Three classes of non-linear loads were considered. Each class is characteri stic for different types of ac to de converters such as the input de s upply used for adjustable-speed-drives, battery chargers, PC's, TV's a nd electronically ballasted Eights, The analysis is based on the deter mination of the most harmonic susceptible busses and their response to each harmonic frequency. A new expeditive method that takes into acco unt the background harmonic voltage phasor, and an equivalent bus impe dance was developed and used to compute the maximum non-linear loads t hat yields VTHD = 5%, (Voltage Total Harmonic Distortion). The main co nclusion of this work is that when mitigation methods are not used, fo r a 15kV class feeder with a maximum 10MVA installed load, the fetal n onlinear residential load should not exceed 300kW if the ITHD < 30% (C urrent Total Harmonic Distortion), and 100kW if ITHD > 100%.