Experimental evaluation of R22 and R407C evaporative heat transfer coefficients in a vapour compression plant

Citation
C. Aprea et al., Experimental evaluation of R22 and R407C evaporative heat transfer coefficients in a vapour compression plant, INT J REFR, 23(5), 2000, pp. 366-377
Citations number
40
Categorie Soggetti
Mechanical Engineering
Journal title
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID
ISSN journal
01407007 → ACNP
Volume
23
Issue
5
Year of publication
2000
Pages
366 - 377
Database
ISI
SICI code
0140-7007(200008)23:5<366:EEORAR>2.0.ZU;2-7
Abstract
The mean heat transfer coefficients of R22 and R407C in the coaxial counter flow evaporator (20 mm ID) of a refrigerating vapour compression plant have been experimentally measured. The experimental conditions under which heat transfer coefficients were determined reflect a typical working situation for small-scale refrigeration systems. The heat flux ranged from 1.9 to 9.1 kW/m(2) and the mass flux was varied from 30 to 140 kg/m(2) s. The results illustrate that the R22 heat transfer coefficient is always greater than t hat of R407C. Furthermore, a comparison carried out between the experimenta l data and those predicted by means of the most credited literature relatio nships showed a strongly overprediction for R407C coefficients. (C) 2000 El sevier Science Ltd and IIR. All rights reserved.