Jn. Wunsche et Jw. Palmer, PORTABLE THROUGH-FLOW CUVETTE SYSTEM FOR MEASURING WHOLE-CANOPY GAS-EXCHANGE OF APPLE-TREES IN THE FIELD, HortScience, 32(4), 1997, pp. 653-658
A monitoring and control system for sequentially measuring whole-tree-
canopy gas exchange of foul apple (Malus domestica Borkh.) trees in th
e field is described. A portable, highly transparent, open-top whole-c
anopy cuvette was developed for complete enclosure of the above-ground
portion of the tree. The flux of whole-canopy CO2 and H2O vapor was e
stimated from differential CO2 concentration and H2O-vapor partial pre
ssure between ambient/reference air entering the cuvette and analysis
air leaving the cuvette, as measured by infrared gas analysis, The bul
k air-flow rate through the chamber was measured with a Pitot static t
ube inserted into the air-supply duct and connected to a differential
pressure transducer. Performance of the whole-canopy cuvette system wa
s tested for its suitability for gas-exchange measurements under field
conditions. The air flow through the whole-canopy cuvette was 22000 L
.min(-1) (approximate to 5.5 air exchanges/min) during the day, provid
ing adequate air mixing within the cuvette, and 4000 L.min(-1) (approx
imate to 1 air exchange/min) during the night. Daily average leaf temp
eratures within the cuvette were 2-3 degrees C higher than to those on
trees outside the cuvette. Photosynthetic photon flux transmitted thr
ough the chamber malls was at least 92% of the incident ambient radiat
ion. Moreover, the whole-canopy cuvette was evaluated without tree enc
losure to determine the degree of ''noise'' in differential CO2 concen
tration and H2O-vapor partial pressure and was found to be acceptable
with Delta CO2 +/- 0.3 mu mol.mol(-1) and Delta H2O +/- 5 Pa. Whole-ca
nopy carbon gas exchange and transpiration of four cropping 'Braeburn'
/M.26 apple trees followed closely incident radiation over the course
of a day.