Reactive power reduction in three-phase electric arc furnace

Citation
A. Wolf et M. Thamodharan, Reactive power reduction in three-phase electric arc furnace, IEEE IND E, 47(4), 2000, pp. 729-733
Citations number
8
Categorie Soggetti
Eletrical & Eletronics Engineeing
Journal title
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
ISSN journal
02780046 → ACNP
Volume
47
Issue
4
Year of publication
2000
Pages
729 - 733
Database
ISI
SICI code
0278-0046(200008)47:4<729:RPRITE>2.0.ZU;2-I
Abstract
A conventional three-phase electric are furnace causes flicker at the point of common coupling with ac mains. This generally occurs with ac mains havi ng a low short-circuit capacity. The flicker is caused by fluctuating react ive power consumption of the furnace. This paper describes a way, through c omputer simulation, of increasing the dynamic performance of the furnace an d keeping reactive power consumption constant. This can be achieved with th e addition of a three-phase power controller and a booster transformer to t he power source and the introduction of a new control method of regulating the reactive power input. The problem of flicker can thus be minimized, Thi s was experimentally tested on a single-phase model and the results obtaine d were very satisfying. Due to Laboratory facilities, the three-phase testi ng was not performed.