The aim of this study is to investigate the required refrigerant speed, hen
ce minimum refrigeration load, for carrying the lubricating oil up in verti
cal sections of refrigerant lines. It is assumed that the downward flow of
the thin oil layer over the inner surface of the riser due to gravity is to
be balanced with the upward flow of the oil film due to the shear force cr
eated by the upward flow of the refrigerant vapor. Velocities are converted
to refrigeration capacities by considering a saturated cycle between speci
fied condenser and evaporator pressures. General relationships thus develop
ed are enumerated for R134a by preparing minimum capacity tables for copper
suction and discharge risers. (C) 2000 Elsevier Science Ltd and IIR. All r
ights reserved.