SURVEY OF HARMONIC VOLTAGE AND CURRENT AT DISTRIBUTION SUBSTATION IN NORTHERN TAIWAN

Citation
Ch. Hu et al., SURVEY OF HARMONIC VOLTAGE AND CURRENT AT DISTRIBUTION SUBSTATION IN NORTHERN TAIWAN, IEEE transactions on power delivery, 12(3), 1997, pp. 1275-1284
Citations number
12
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
12
Issue
3
Year of publication
1997
Pages
1275 - 1284
Database
ISI
SICI code
0885-8977(1997)12:3<1275:SOHVAC>2.0.ZU;2-L
Abstract
This paper presents a survey of voltage and current harmonic distortio n levels at 40 power transformers and 10 capacitor units in Northern T aiwan. Through one year measurement, about 12,000 sets of harmonic vol tage and current data are recorded and analyzed. The types and levels of harmonics are showed in each power transformer which supplies diffe rent residential, commercial, and industrial customers with various lo ads. At the same time, a suggestion is given to the representative val ue of background level of harmonic voltages with 95% cumulative probab ility which is adopted by Taipower. At last, effects of harmonics on c apacitors and power transformers are discussed.