Cc. Wang et al., Effect of waffle height on the air-side performance of wavy fin-and-tube heat exchangers under dehumidifying conditions, HEAT TR ENG, 21(5), 2000, pp. 17-26
An experimental study was carried out to examine the effect of the waffle h
eight on air-side performance of typical fin-and-tube heat exchangers under
dehumidifying conditions. The waffle heights examined in the present study
are 1.18 and 1.58 mm, respectively. A total of 12 samples of heat exchange
rs, including eight having wavy fin and four having plain fin configuration
s were tested. The test results indicated that the effect of waffle height
on the heat transfer enhancement ratio, compared to the plain-fin counterpa
rt, is pronounced only for smaller fin pitch and larger waffle height, whil
e its effect on the pressure drop is very pronounced throughout the lest ra
nge, and is almost two times higher than in dry conditions.