This paper brings out the existence of the maximum in the curvature of the
vapour pressure curve. It occurs in the reduced temperature range of 0.6-0.
7 for all liquids and has a value of 3.8-4.8. A set of 17 working fluids co
nsisting of several refrigerants, carbon dioxide, cryogenic liquids and wat
er are taken as test fluids. There exists also a minimum dose to the critic
al point which can be observed only when a thermodynamically consistent fun
ctional form of the vapour pressure equation is chosen. This feature, in ad
dition to throwing some light on the behaviour of the vapour pressure curve
, could provide some useful inputs to the choice of working fluids for vapo
ur pressure thermometers and thermostatic expansion valves, (C) 2001 Elsevi
er Science B.V. All rights reserved.