In this study, in-situ performance test of a 20 RT (70 kW) air-to-air heat
pump which has a feature of recovering ventilation energy is carried out. S
ince test conditions such as indoor and outdoor air conditions cannot be co
ntrolled to satisfy the standard test conditions, experiments are done with
the inlet air conditions as they exist. From the experimental data obtaine
d with the non-standard test conditions, simulation program is developed to
estimate the performance of standard test conditions. The map-based compre
ssor model, epsilon -NTU method with the assumption of refrigerant-side mix
ed and air-side unmixed and necessary parameters determined from the measur
ements are used. From the simulation, performance of a large capacity air s
ource heat pump for various conditions and effects of ventilation are calcu
lated. This study provides method of predicting the performance of air sour
ce heat pumps in which in-situ performance test is necessary.