B. Decker et U. Jahn, PERFORMANCE OF 170 GRID CONNECTED PV PLANTS IN NORTHERN GERMANY - ANALYSIS OF YIELDS AND OPTIMIZATION POTENTIALS, Solar energy, 59(4-6), 1997, pp. 127-133
Within the German 1000 roof PV programme, about 2000 grid connected PV
plants (1-5 kW(p)) with a total peak power of 5 MWp were installed on
the roofs of single and two family houses. In the Federal State of Lo
wer Saxony, ISFH has been responsible for the technical inspections an
d the global monitoring of 172 PV plants up until now. The annual fina
l yields range between 430 kWh/(kW(p)a) and 875 kWh/(kW(p)*a) with a
mean value of 680 kWh/(kW(p)a). Using the annual in-plane irradiation
, we determine annual performance ratios in the range 47.5%-81% (mean
66.5%). A procedure to receive standardized performance ratios is intr
oduced using actual peak powers of the PV modules and inverter-specifi
c efficiencies. Typical curves of monthly values of the performance ra
tio are recorded. PV plants with low final yields are analyzed with re
spect to operational failures, partly shadowing effects, and poorness
in maximum power point adaptation of some inverters. Optimization pote
ntials are also discussed. (C) 1997 Elsevier Science Ltd.