Design considerations on the line-side filter used in the dynamic voltage restorer

Citation
Bh. Li et al., Design considerations on the line-side filter used in the dynamic voltage restorer, IEE P-GEN T, 148(1), 2001, pp. 1-7
Citations number
15
Categorie Soggetti
Eletrical & Eletronics Engineeing
Journal title
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION
ISSN journal
13502360 → ACNP
Volume
148
Issue
1
Year of publication
2001
Pages
1 - 7
Database
ISI
SICI code
1350-2360(200101)148:1<1:DCOTLF>2.0.ZU;2-V
Abstract
The effects of harmonic voltages generated by the voltage-source inverter w ithin a dynamic voltage restorer can be mitigated through the use of a line -side filter. However, injudicious design of the harmonic-filtering system can degrade the power-quality-enhancement capability of the restorer. Inapp ropriate filter design may also result in the need for the inverter current rating to be increased significantly. The purpose of the investigation is therefore to carry out a systematic analysis of the filter design by consid ering first the selection of the filter-capacitor on the basis of meeting a prespecified harmonic-performance criterion. The effect of the capacitor o n the inverter rating is then evaluated and the method of determining the f ilter capacity is presented. An example, which involves electromagnetic tra nsient studies, is included to demonstrate the efficacy of the proposed des ign method.