Influence of fault arc characteristics on the accuracy of digital fault locators

Citation
T. Funabashi et al., Influence of fault arc characteristics on the accuracy of digital fault locators, IEEE POW D, 16(2), 2001, pp. 195-199
Citations number
17
Categorie Soggetti
Eletrical & Eletronics Engineeing
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
ISSN journal
08858977 → ACNP
Volume
16
Issue
2
Year of publication
2001
Pages
195 - 199
Database
ISI
SICI code
0885-8977(200104)16:2<195:IOFACO>2.0.ZU;2-A
Abstract
This paper has proposed a time domain model of a fault locator with special reference to fault are nonlinearities by applying the MODELS language of t he EMTP. It has been found that an impedance relay type locator is signific antly influenced by the fault are nonlinearities, while the current diversi on ratio method is not influenced, This validates the advantage of the curr ent diversion approach over the impedance approach.