This paper deals with the evaluation of the insulation design of polymer ho
used surge arresters for distribution lines. Five commercial designs were t
ested in a salt fog chamber for 9 cycles using a cycle consisting of 120 ho
urs of salt fog that was followed by a 48 hour rest period for a total of 1
280 hours of salt fog, In these tests, the specification for the 1000-hour
salt fog test in EC 1109 for composite insulators was used as a guide. The
results demonstrate that a comprehensive evaluation of the external and int
ernal insulation design of pollymer housed surge arresters can be obtained
by performing a salt fog test, and as such, the test can be considered as a
useful design test, Suggestions for improvements in the insulation design
of all polymer housed surge arresters evaluated are given in the paper.