We have developed a 22kV16.9kV HTS single-phase transformer cooled by liqui
d nitrogen for field test, which is a practical model for the single-phase
part of a 3MVA HTS power transformer. First, we numerically simulated elect
romagnetic, mechanical and thermal conditions of the windings in accidental
cases of short-circuit and lightning impulse, and considered the winding s
tructure withstanding the severe loads, We constructed a small-sized model
coil of Bi-2223 Ag/Mn-sheathed tapes and confirmed applicability of the des
ign concept for the over-current and high-withstand-voltage tests. We desig
ned and constructed a single-phase HTS transformer on the basis of the mode
l-coil-test results. The primary and secondary windings are transposed para
llel conductors of two and six Bi-2223 Ag/Mn tapes, respectively. The same
tests for the HTS transformer as for usual oil-filled ones indicated the re
liable operation and high performance. The field test in a distribution gri
d of Kyushu Electric Power Co. included inrush-current test and long-term o
peration of the transformer cooled by a continuous supply system of subcool
ed liquid nitrogen with cryocoolers.