Study on recovery time of a superconducting fault current limiter with adjustable trigger current level

Citation
Y. Shirai et al., Study on recovery time of a superconducting fault current limiter with adjustable trigger current level, IEEE APPL S, 11(1), 2001, pp. 2086-2089
Citations number
7
Categorie Soggetti
Apllied Physucs/Condensed Matter/Materiales Science
Journal title
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY
ISSN journal
10518223 → ACNP
Volume
11
Issue
1
Year of publication
2001
Part
2
Pages
2086 - 2089
Database
ISI
SICI code
1051-8223(200103)11:1<2086:SORTOA>2.0.ZU;2-V
Abstract
The recovery time of a transformer type SCFGL (Superconducting Fault Curren t Limiter) with adjustable trigger current level, is studied experimentally . The recovery time is defined as the required time of zero current period of SCFCL for recovery from its current limiting mode to its waiting mode. A trial SCFCL, which was designed and made, Is tested to measure the recover y time with various fault time. The experimental results show that the reco very time depends on the fault time. When the fault time is longer than 200 ms, the recovery time becomes shorter and approaches a certain value (a fe w ten ms) as the fault time is longer.