DEVELOPMENT OF 500-KV XLPE CABLES AND ACCESSORIES FOR LONG-DISTANCE UNDERGROUND TRANSMISSION-LINE .1. INSULATION DESIGN OF CABLES

Citation
T. Kubota et al., DEVELOPMENT OF 500-KV XLPE CABLES AND ACCESSORIES FOR LONG-DISTANCE UNDERGROUND TRANSMISSION-LINE .1. INSULATION DESIGN OF CABLES, IEEE transactions on power delivery, 9(4), 1994, pp. 1741-1749
Citations number
12
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
9
Issue
4
Year of publication
1994
Pages
1741 - 1749
Database
ISI
SICI code
0885-8977(1994)9:4<1741:DO5XCA>2.0.ZU;2-I
Abstract
This paper discusses the results of a basic study for the development of 500-kV XLPE cables. The authors have established that the factors t hat decide the performance of today's XLPE cables are impurities in th e insulator and protrusions on the semiconductive layer, and that the insulation performance of XLPE cables is determined by the size of the se defects. In model tests of XLPE cables, the minimum insulation brea kdown stress of cables was determined, to set the design values for 50 0-kV XLPE cable. As a result, it was found that it is possible to desi gn cables having an insulation thickness of 25 mm.