DIRECTIONAL SENSITIVITY TO GEOMAGNETICALLY INDUCED CURRENTS OF THE HYDRO-QUEBEC 735-KV POWER-SYSTEM

Citation
Dh. Boteler et al., DIRECTIONAL SENSITIVITY TO GEOMAGNETICALLY INDUCED CURRENTS OF THE HYDRO-QUEBEC 735-KV POWER-SYSTEM, IEEE transactions on power delivery, 9(4), 1994, pp. 1963-1971
Citations number
13
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
9
Issue
4
Year of publication
1994
Pages
1963 - 1971
Database
ISI
SICI code
0885-8977(1994)9:4<1963:DSTGIC>2.0.ZU;2-B
Abstract
To examine the sensitivity to geomagnetically induced currents (GIC) o f the Hydro-Quebec 735 kV power system, model calculations were made o f the GIC produced by uniform electric fields directed northwards (azi muth of 0-degree) and with azimuths increasing in 15-degrees increment s. The results show that the maximum GIC was produced in the system fo r an electric field bearing 15-degrees. In addition the model results allow the variation of GIC amplitude with electric field direction to be examined for individual substations. Maximum GIC occurred at substa tions at the ends of a long transmission line when the electric field was aligned with the transmission line.