OPERATION OF GROUND SENSOR RELAYS UNDER CONDITIONS OF PARTIAL CT SATURATION

Citation
B. Bridger et Ta. Burse, OPERATION OF GROUND SENSOR RELAYS UNDER CONDITIONS OF PARTIAL CT SATURATION, IEEE transactions on industry applications, 33(4), 1997, pp. 1111-1116
Citations number
4
Categorie Soggetti
Engineering,"Engineering, Eletrical & Electronic
ISSN journal
00939994
Volume
33
Issue
4
Year of publication
1997
Pages
1111 - 1116
Database
ISI
SICI code
0093-9994(1997)33:4<1111:OOGSRU>2.0.ZU;2-T
Abstract
Since the publication of the paper by Barnett, et al. [1], concerning low-ratio CT saturation at high fault current and resulting misoperati on or nonoperation of overcurrent relays, there has been a great deal of well-directed concern about the problem reported in that paper. How ever, some of that concern has also been directed at the application o f ground sensor relays to low-ratio CT's in resistance grounded indust rial power systems, where no operational difficulties have been report ed. The authors conducted a series of tests to determine if there is a ny cause for concern. These tests documented both the CT secondary cur rent wave shapes and the relay contact closure times for several CT-re lay-fault current combinations. This paper reports the results of thes e tests and presents conclusions concerning the adequacy of present pr actice in this field.