Hc. Chang et Tt. Chang, Optimal installation of three-phase active power line conditioners in unbalanced distribution systems, ELEC POW SY, 57(3), 2001, pp. 163-171
In this paper, a new solution algorithm based on a multiple gradient summat
ion (MGS) and differential evolution (DE) approach for optimal three-phase
active power line conditioners (APLCs) installation in unbalanced distribut
ion systems is proposed. The active power line conditioners installation pr
oblem considers the individual and total harmonic voltage distortions as we
ll as the commercially available discrete sizes of the APLCs limits to mini
mize the total sizes of three-phase APLCs. The imbalance of systems resulti
ng from using asymmetrical connection transformers was taken into account.
The effectiveness of the proposed method was demonstrated by its applicatio
n to a 23-bus unbalanced radial distribution system. (C) 2001 Elsevier Scie
nce B.V. All rights reserved.