The hydraulic characteristics of sub-cooled nitrogen in superconducting pow
er transmission line have been investigated to design the transmission line
. To estimate the friction factor in corrugated pipes, the pressure drop wa
s measured across a 10-m length corrugated pipe for various mass flow rates
and compared with that in smooth pipes (Proc. 17th Cryo. Eng. Conf. (1998)
475). Another concern is the cooling method of the transmission line. A us
ual counter-flow cooling method has been found to be very difficult at liqu
id nitrogen temperature, because the thermal conductivity of the dielectric
materials between the counter-flows at liquid nitrogen temperature are 10
times larger than that at liquid helium temperature. Instead, an externally
cooling method was proposed (Proc. 17th Cryo. Eng. Conf. (1998) 475). As t
he results, the friction factor of outer corrugated jacket within three cab
les has become an important parameter to design the transmission lines. Thi
s friction factor is measured and compared with various formulas in this pa
per. (C) 2001 Elsevier Science B.V. All rights reserved.