Closed-loop identification and control application for dissolved oxygen concentration in a full-scale coke wastewater treatment plant

Citation
Ck. Yoo et al., Closed-loop identification and control application for dissolved oxygen concentration in a full-scale coke wastewater treatment plant, WATER SCI T, 43(7), 2001, pp. 207-214
Citations number
12
Categorie Soggetti
Environment/Ecology
Journal title
WATER SCIENCE AND TECHNOLOGY
ISSN journal
02731223 → ACNP
Volume
43
Issue
7
Year of publication
2001
Pages
207 - 214
Database
ISI
SICI code
0273-1223(2001)43:7<207:CIACAF>2.0.ZU;2-B
Abstract
The objective of this paper is to apply a closed-loop identification to act ual dissolved oxygen control system in the coke wastewater treatment plant. It approximates the dissolved oxygen dynamics to a high order model using the integral transform method and reduces it to the first-order plus time d elay (FOPTD) or second-order plus time delay (SOPTD) for the PID controller tuning. To experiment the process identification on the real plant, a simp le set-point change of the speed of surface aerator under the closed-loop c ontrol without any mode change was used as an activation signal of the iden tification. The full-scale experimental results show a good identification performance and a good tracking ability for set-point change. As a result o f improved control performance, the fluctuation of dissolved oxygen concent ration variation has been decreased and the electric power saving has been accomplished.