Ck. Yoo et al., Closed-loop identification and control application for dissolved oxygen concentration in a full-scale coke wastewater treatment plant, WATER SCI T, 43(7), 2001, pp. 207-214
The objective of this paper is to apply a closed-loop identification to act
ual dissolved oxygen control system in the coke wastewater treatment plant.
It approximates the dissolved oxygen dynamics to a high order model using
the integral transform method and reduces it to the first-order plus time d
elay (FOPTD) or second-order plus time delay (SOPTD) for the PID controller
tuning. To experiment the process identification on the real plant, a simp
le set-point change of the speed of surface aerator under the closed-loop c
ontrol without any mode change was used as an activation signal of the iden
tification. The full-scale experimental results show a good identification
performance and a good tracking ability for set-point change. As a result o
f improved control performance, the fluctuation of dissolved oxygen concent
ration variation has been decreased and the electric power saving has been
accomplished.