The purpose of this paper is to analyze the torsional stability of a t
urbogenerator, in a case in which, with a.c. 400 kV cable transmission
lines, it is necessary to provide shunted compensation. The problem i
s brought into focus from the physical point of view by means of a sim
plified schematic operating presentation. This simplified analysis is
then validated by means of a computer program for the dynamic study of
the electromechanical system, applied to an example consisting of a t
urbine shaft, the alternator, the excitation control system, a step-up
transformer, and a cable line with shunt compensation and connected t
o a prevalent power node. Both the methods of analysis show that, unli
ke the dual case of the series compensation of overhead lines, in this
case conditions of torsional instability do not occur.