In situ corrosion control in industrial water systems

Citation
Jf. Batista et al., In situ corrosion control in industrial water systems, BIODEGRADAT, 11(6), 2000, pp. 441-448
Citations number
11
Categorie Soggetti
Biotecnology & Applied Microbiology
Journal title
BIODEGRADATION
ISSN journal
09239820 → ACNP
Volume
11
Issue
6
Year of publication
2000
Pages
441 - 448
Database
ISI
SICI code
0923-9820(2000)11:6<441:ISCCII>2.0.ZU;2-V
Abstract
The main objective of this study was to evaluate the efficacy of a biocide and a corrosion inhibitor against the corrosion of a circulating pipe in a cooling tower. Isothiazolone was tested as the industrial biocide. The resu lts showed that the biocide by itself or combined with a dispersant was not efficient to control corrosion in the industrial system. Corrosion rates o f 0.324 mm/year were recorded in both the presence and absence of the bioci de. Corrosion control was successfully accomplished by using a corrosion in hibitor. In the latter case the maximum corrosion rate of 0.024 mm/year wer e obtained.