The main objective of this study was to evaluate the efficacy of a biocide
and a corrosion inhibitor against the corrosion of a circulating pipe in a
cooling tower. Isothiazolone was tested as the industrial biocide. The resu
lts showed that the biocide by itself or combined with a dispersant was not
efficient to control corrosion in the industrial system. Corrosion rates o
f 0.324 mm/year were recorded in both the presence and absence of the bioci
de. Corrosion control was successfully accomplished by using a corrosion in
hibitor. In the latter case the maximum corrosion rate of 0.024 mm/year wer
e obtained.