D. Zaruk et al., Comparison of immunoassay with a conventional method for the determinationof Diazinon (R) in surface waters, ANALYT CHIM, 444(1), 2001, pp. 163-168
The National Laboratory for Environmental Testing (NLET) has successfully u
sed immunoassay as a screening technique to detect the presence of organic
contaminants. A Beacon Analytical Systems Inc., InSite (TM) Diazinon Plate
Kit was tested for its ability to identify Diazinon((R)) {O,O-diethyl-O-(2[
-methylethyl]4-methyl-6-pyrimidinyl)phosphorothioate} in a surface water kn
own to have agricultural inputs from organophosphate pesticide (OP) applica
tions. The quantitative accuracy of test kit results were compared against
the conventional NLET gas chromatography (GC) method. Of 21 OP observations
using the conventional method, 15 were at or below the detection limit of
the immunoassay kit, 4 were observed and 2 were not detected. There were no
false positives, but overall precision amongst immunoassay replicates was
poor (CV > 50%). All immunoassay results were biased high compared to their
corresponding GC concentrations. Of the four immunoassay observations, thr
ee had GC concentrations below the detection limit of the test kit, which w
ould imply these immunoassay values included responses due to cross-reactiv
ity with other compounds. Based on the limited data set, application of imm
unoassay for screening the presence of diazinon at our test site did not ap
pear favorable. Differences in sample storage conditions were not expected
to contribute to differences, but may have to be re-examined. (C) 2001 Else
vier Science B.V. All rights reserved.