A hybrid mass damper system with convertible active and passive modes using
a hydraulic actuator (hereinafter referred to as APMD) has been installed
to an actual slender tall building with an aspect ratio of eight constructe
d in Chiba prefecture. In this paper, simulation analysis, force vibration
tests and observation of behaviours against moderate wind or some earthquak
e excitations were carried out to investigate the response control performa
nce of the mass damper system. From the analysis, it was confirmed that on
the active mode due to the vibration tests, the damping factors in the 1st
mode were about 8-11 per cent, the satisfactory vibration control effect wa
s obtained, and no spillover in the second mode occurred. The response valu
es of the peak and the R.M.S. accelerations under the active mode due to th
e actual wind excitations were reduced to 1/4.5-1/2.0 (average 1/3) in comp
arison with the responses in non-controlled system. Through the results obt
ained by these investigations, it was concluded that the mass damper system
was quite effective for the response control of the slender tall building
to wind loads or earthquakes. Copyright (C) 2001 John Wiley & Sons, Ltd.