Pressure drop measurements in condensing steam over a horizontal bundle ofstaggered tubes

Citation
Bm. Burnside et al., Pressure drop measurements in condensing steam over a horizontal bundle ofstaggered tubes, INT J TH SC, 40(10), 2001, pp. 917-926
Citations number
15
Categorie Soggetti
Mechanical Engineering
Journal title
INTERNATIONAL JOURNAL OF THERMAL SCIENCES
ISSN journal
12900729 → ACNP
Volume
40
Issue
10
Year of publication
2001
Pages
917 - 926
Database
ISI
SICI code
1290-0729(200110)40:10<917:PDMICS>2.0.ZU;2-7
Abstract
Pressure drop measurements in a 15 row staggered configuration condenser, p /D = 1.33, are described. Heat flux densities of up to 90 kW(.)m(-2) were u sed. The results are compared with the those of another investigation using a condenser with much less closely packed tubes. At relatively low suction , pressure drop in the closely packed condenser could be predicted by conve ntional single phase correlations. At higher values of suction the condensi ng pressure toss was considerably lower in this condenser than the single p hase value. In the more loosely packed condenser this difference occurred a t all values of suction. It is concluded that more experimental and theoret ical work is required to explain these effects in view of their importance in turbine condenser design. (C) 2001 Editions scientifiques et medicales E lsevier SAS.