Control/maintenance strategy fault tolerant mode and reliability analysis for hydro power stations

Citation
Lq. Ye et al., Control/maintenance strategy fault tolerant mode and reliability analysis for hydro power stations, IEEE POW SY, 16(3), 2001, pp. 340-345
Citations number
6
Categorie Soggetti
Eletrical & Eletronics Engineeing
Journal title
IEEE TRANSACTIONS ON POWER SYSTEMS
ISSN journal
08858950 → ACNP
Volume
16
Issue
3
Year of publication
2001
Pages
340 - 345
Database
ISI
SICI code
0885-8950(200108)16:3<340:CSFTMA>2.0.ZU;2-Y
Abstract
Reliability analysis for hydro power stations for (N + M) and 2N fault tole rant modes (FTM) and their comparison from the standpoint of control and ma intenance have been carried out in this paper, it shows that the (N + M) FT M is superior to 2N FTM in reliability and economics in most cases. So, (N + IM) FTM is recommended for large power stations, especially for multi-uni t plants, A simple method to choose the number of standby controllers is de veloped by optimizing the (N + M) FTM. The ideas and results proposed in th is paper can be used not only for governing systems in hydro power stations but also for other industrial systems.