The heating effects at the end-ring connection areas of the rotor due
to the harmonic current generation of a saturating unit transformer fr
om geomagnetic induced currents (GIC) on the transmission system have
been calculated from observed data and from EMTP studies sponsored by
the Electric Power Research Institute. These calculations show that da
mage may occur during strong GIC storm activity. This damage can occur
from unit transformer saturation or other transformers in the system
near the generator. The possibility of damage should be monitored duri
ng strong GIC storms through the use of appropriate negative- sequence
current monitoring and alarms.