LOCAL TEMPERATURE-MEASUREMENTS IN A FULL-SCALE UTILITY BOILER WITH OVERFIRE AIR

Authors
Citation
Dr. Tree et Bw. Webb, LOCAL TEMPERATURE-MEASUREMENTS IN A FULL-SCALE UTILITY BOILER WITH OVERFIRE AIR, Fuel, 76(11), 1997, pp. 1057-1066
Citations number
18
Categorie Soggetti
Energy & Fuels","Engineering, Chemical
Journal title
FuelACNP
ISSN journal
00162361
Volume
76
Issue
11
Year of publication
1997
Pages
1057 - 1066
Database
ISI
SICI code
0016-2361(1997)76:11<1057:LTIAFU>2.0.ZU;2-B
Abstract
Gas temperature and effluent NOx measurements were obtained in a full- scale (160 MWe) pulverized coal corner-fired utility boiler with separ ate overfire air. The measurements are the first of this kind in a ful l-scale boiler operated with overfire air and low-NOx burners. A test matrix of seven operating conditions was used to compare temperature a nd NOx with changes in overfire air, coal type, load and burner tilt. Peak temperatures were 1500-1600 degrees C and occurred just above the top burner. The measurements detailed the profile of temperature thro ugh a traverse of a coal burner, close-coupled overfire air port and s eparate overfire port. The data in the near-burner and overfire air re gions showed evidence of reduced swirl as overfire air was increased. Little difference was seen in the temperatures for two coals with vola tile fractions of 28 and 36 wt%. Temperature changes were quantified i n the overfire air region for changes in burner tilt and load. Tempera ture was approximately the same in the overfire air region as load was decreased, but increased in this region as the burners were tilted fr om +5 degrees to -5 degrees. (C) 1997 Elsevier-Science Ltd.