Jj. Shea et Ja. Bindas, MEASURING MOLDED CASE CIRCUIT-BREAKER RESISTANCE, IEEE transactions on components, hybrids, and manufacturing technology, 16(2), 1993, pp. 196-202
Citations number
10
Categorie Soggetti
Material Science","Engineering, Eletrical & Electronic
Molded case circuit breaker resistance was measured under various cond
itions to demonstrate the need for more standardized procedures when p
erforming millivolt drop measurements. Breakers, rated at 600 V(ac)/25
0 A(ac) and 120/240 V(ac)/50 A(ac), with silver-tungsten (Ag-W) contac
ts were used to show that contact resistance can cause variability in
circuit breaker resistance. These breakers were used to demonstrate th
e influence of current, time, contact temperature, and applied voltage
on contact resistance. These parameters each had a unique influence o
n breaker resistance. Based on these results, guidelines were made for
making reliable resistance measurements on molded case circuit breake
rs (MCCB's) when using the millivolt drop technique.