Performance of wire-on-tube heat exchangers used in immersion cooling for electronic packages

Citation
Ga. Quadir et al., Performance of wire-on-tube heat exchangers used in immersion cooling for electronic packages, PROCEEDINGS OF 3RD ELECTRONICS PACKAGING TECHNOLOGY CONFERENCE, 2000, pp. 445-451
Citations number
6
Categorie Soggetti
Current Book Contents
Year of publication
2000
Pages
445 - 451
Database
ISI
SICI code
Abstract
In the preset investigation, a closed loop immersion cooling of an electron ic package with external condenser-a wire-on-tube heat exchanger being atta ched to its enclosure, is analysed. The dielectric vapour leaving the enclo sure flows through the tubes of the heat exchanger. The vapour is cooled by ambient air in free or forced convection environment. The finite element method is used in the analysis. The dielectric fluid use d is FC-72. The effects of parameters like the length of the tube, ambient temperature, mass flow rate of the dielectric fluid, etc, on the performanc e of the heat exchanger have been studied. The results are also presented i n the form of epsilon -NTU curves. The proposed method may be used to check the adequacy of the number of tubes provided in the existing wire-on-tube heat exchangers for complete condensation of the vapour when the operating conditions are different from the design conditions.